Generator Stator Earth Fault Relay .
-For high impedance grounded generators, a voltage relay across the sec**dary winding of the Generator neutral grounding transformer is used to detect the ground fault ** the generator stator winding. -The neutral over voltage functi** (59N) resp**ds to the fundamental frequency voltage at the generator neutral that appears when a ground fault occurs. -Normally, it will protect up to 90≈ 95 % of the stator windings. -The neutral under voltage functi**s resp**ds to 3rd harm**ic voltage measured at the generator neutral. When used in c**juncti** with the neutral over voltage functi**, it provides 100% ground fault protecti** of the stator winding.